UPS.CONF(5)                 Network UPS Tools (NUT)                UPS.CONF(5)



NAME
       ups.conf - UPS definitions for Network UPS Tools


DESCRIPTION
       This  file  is read by the driver controller upsdrvctl, the UPS drivers
       that use the common core (see  nutupsdrv(8))  and  upsd(8).   The  file
       begins  with  global  directives, and then each UPS has a section which
       contains a number of directives that set parameters for that UPS.

       A UPS section begins with the name of the ups in brackets, and  contin-
       ues  until  the  next  UPS  name  in  brackets  or until EOF.  The name
       "default" is used internally in upsd, so you can't use it in this file.

       You must define the "driver" and "port" elements for each entry.   Any-
       thing after that in a section is optional.  A simple example might look
       like this:


                   [myups]
                        driver = megatec
                        port = /dev/ttyS0
                        desc = "Web server UPS"

       A slightly more complicated version includes some extras for the  hard-
       ware-specific part of the driver:


                   [bigups]
                        driver = apcsmart
                        port = /dev/cua00
                        cable = 940-0095B
                        sdtype = 2
                        desc = "Database server UPS"

       In  this  case,  the  apcsmart(8)  driver will receive variables called
       "cable" and "sdtype" which have special meanings.  See the man pages of
       your driver(s) to learn which variables are supported and what they do.


GLOBAL DIRECTIVES
       chroot Optional.   The  driver  will chroot(2) to this directory during
              initialization.  This can be useful when securing systems.


       driverpath
              Optional.  Path name of the directory in which  the  UPS  driver
              executables  reside.   If  you  don't specify this, the programs
              look  in  a  built-in  default   directory,   which   is   often
              /usr/local/ups/bin.


       maxstartdelay
              Optional.   Same  as the UPS field of the same name, but this is
              the default for UPSes that don't have the field.


       pollinterval
              Optional.  The status of the UPS will be refreshed after a maxi-
              mum delay which is controlled by this setting.  This is normally
              2 seconds.  This may be useful if the  driver  is  creating  too
              much of a load on your system or network.


       user   Optional.   If started as root, the driver will setuid(2) to the
              user id associated with username.


UPS FIELDS
       driver Required.  This specifies which program will be monitoring  this
              UPS.   You  need to specify the one that is compatible with your
              hardware.  See nutupsdrv(8) for more information on  drivers  in
              general and pointers to the man pages of specific drivers.


       port   Required.   This  is the serial port where the UPS is connected.
              On a Linux system, the first serial port usually is  /dev/ttyS0.
              On FreeBSD and similar systems, it probably will be /dev/cuaa0.


       sdorder
              Optional.  When you have multiple UPSes on your system, you usu-
              ally need to turn them off in a certain order.  upsdrvctl  shuts
              down  all  the 0s, then the 1s, 2s, and so on.  To exclude a UPS
              from the shutdown sequence, set this to -1.

              The default value for this parameter is 0.


       desc   Optional.  This allows you to set a brief description that  upsd
              will  provide to clients that ask for a list of connected equip-
              ment.


       nolock Optional.  When you specify this,  the  driver  skips  the  port
              locking  routines  every  time  it starts.  This may allow other
              processes to seize the port if you start more than one  acciden-
              tally.

              You should only use this if your system won't work without it.

              This may be needed on Mac OS X systems.


       maxstartdelay
              Optional.  This can be set as a global variable above your first
              UPS definition and it can also be set in a  UPS  section.   This
              value  controls  how  long upsdrvctl will wait for the driver to
              finish starting.  This keeps your system from getting stuck  due
              to a broken driver or UPS.

              The default is 45 seconds.

       All  other  fields  are passed through to the hardware-specific part of
       the driver.  See those manuals for the list of what is allowed.


INTEGRATION
       upsdrvctl(8) uses this file to start and stop the drivers.

       The drivers themselves also obtain configuration data from  this  file.
       Each driver looks up its section and uses that to configure itself.

       upsd(8)  learns about which UPSes are installed on this system by read-
       ing this file.  If this  system  is  called  "doghouse"  and  you  have
       defined a UPS in your ups.conf called "snoopy", then you can monitor it
       from upsc(8) or similar as "snoopy@doghouse".


SEE ALSO
       upsd(8), nutupsdrv(8), upsdrvctl(8)


   Internet resources:
       The NUT (Network UPS Tools) home page: http://www.networkupstools.org/



                                Sun Aug 24 2003                    UPS.CONF(5)